6.4 Mixing Wire & Fiber on One Network
In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable. Use a HS-NCM-WMF/WMF-2 or HS-NCM-WSF/WSF-2 as an
interface between wire and fiber.
Fiber ports are not polarity sensitive. However, port-to-port wiring for the HS-NCM wire connections are polarity sensitive. When converting from a
wire to fiber network, it may be necessary to change the port designation for the wire connection on the HS-NCM-WMF/WSF/WMF-2/WSF-2. To
change the wire port designation, the HS-NCM parameters must be changed via VeriFire Tools. For instructions on how to change the HS-NCM
parameters, refer to “HS-NCM Configuration” on page 6.
See Section 2.1, “Network Communications Module for Fiber (HS-NCM-MF, HS-NCM-SF, HS-NCM-MFSF)” for requirements and restrictions on
the use of fiber-optic cable. See the High-Speed
Noti•Fire•Net Manual for a discussion of all compatible configurations.
6.5 Approved Cables and Distances
6.5.1 HS-NCM-W Applications
The following table shows approved wiring cables that can be used with the HS-NCM and the maximum total distance allowed for each.
Wire Type / Gauge Maximum Distance: Wire Type / Gauge Maximum Distance
Aerospace 7131KK / 16 AWG 2000 ft. (609.6 m.) Genesis 4631 / 18 AWG 3,000 ft. (914.4 m)
Belden 5220UM / 16 AWG 1,000 ft. (304.8 m) Genesis 4633 / 14 AWG 3,000 ft. (914.4 m)
Belden 5320UJ / 18 AWG 3,000 ft. (914.4 m) Genesis 5502 / 16 AWG 1,000 ft. (304.8 m)
Belden 5320UM / 18 AWG 3,000 ft. (914.4 m) Lake Cable SNY141PR-NOT / 14 AWG 1,200 ft (365.8 m)
Comtran 8696 / 18 AWG 1,000 ft. (304.8 m) Pyrotenax 2/16-246T / 16 AWG 425 ft (129.5 m)
Comtran 8698 / 14 AWG 1,000 ft. (304.8 m) Radix CI14A0702-0000-I5000 / 14 AWG 1,500 ft (457.2 m)
Comtran 8706 / 16 AWG 1,000 ft. (304.8 m) Radix CI16A0102-0000-I5000 / 16 AWG 1,600 ft (487.6 m)
Comtran 8709 / 14 AWG 1,000 ft. (304.8 m) Radix DuraLife 18A0102 Unshielded
18AWG
1,000 ft (305.8m)
Comtran 35777 VITALink 2C/16 /
16 AWG
850 ft (259.0 m) Radix DuraLife 16A0102 Unshielded
16AWG
1,000 ft (305.8m)
Comtran 35787 14AWG 850 ft (259.0 m) Shawflex 64220M140118700 / 14 AWG 250 ft (76.2 m)
Comtran 36316 VITALink Shielded twisted-
pair 14AWG FPLR-CI
1,000 ft (304.8 m) West Penn AQ225 / 16 AWG 1,000 ft (304.8 m)
Draka USA C FLPR-2C/16NS / 16 AWG 1,000 ft. (304.8 m) West Penn D980 / 18 AWG 2,000 ft (609.6 m)
Genesis 4050 / 18 AWG 3,000 ft. (914.4 m) West Penn D990 / 16 AWG 2,000 ft (609.6 m)
Genesis 4431 / 18 AWG 2,000 ft. (609.6 m) Windy City Wire / 16 AWG 900 ft. (274.32 m)
Genesis 4433 / 14 AWG 3,000 ft. (914.4 m)
Table 4 Maximum Distance for Approved Cables
To Next
HS-NCM-MF/SF
HS-NCM-W
HS-NCM-WMF/WSF
HS-NCM-MF/SF/MFSF
U9
Channel B
U8
Channel A
U9
Channel B
U8
Channel A
From Previous
HS-NCM-W
Figure 16 Wire-to-Fiber Connections