High-Speed Network Communications Module
Product Installation Document
PN 54014:C1 12/15/2020 ECN: 151329
WARNING
Adhere to the following To Avoid Permanent Damage:
When installing a HS-NCM (High-Speed Network Communications Module) on high-speed networks and workstations, adhere to the following to
avoid permanent damage:
Do not attempt to upgrade HS-NCM to software v30.x (or higher) on a network that utilizes v20 HS-NCMs using v20.4 (or lower) software. This
will result in permanent damage to all v20 HS-NCMs on the network
Attempting to individually upgrade any v20 HS-NCM with software V30.x (or higher) will result in permanent damage
When using v30 HS-NCM, VeriFire Tools v8.20 (or higher) is required for all HS-NCM software upgrades
When using an Ethernet cable (RJ45) to bridge a VDSL network with a BoradR-Reach network use VeriFire Tools version 10.80 (or higher)
When a HS-NCM-W-2, HS-NCM-WMF-2 or HS-NCM-WSF-2 is used in a network use VeriFire Tools version 10.80 (or higher)
1 Product Overview
The High-Speed Network Communications Module (HS-NCM) provides a means for connecting specific Notifier fire alarm control products to High-
Speed NOTI•FIRE•NET™. There are six types of HS-NCMs available: HS-NCM-W/W-2 for connecting nodes with twisted-pair wire; HS-NCM-MF
and HS-NCM-SF are used for connecting nodes with fiber-optic cable; HS-NCM-WMF/WMF-2 and HS-NCM-WSF/WSF-2 are used for connecting
nodes with fiber-optic cables to nodes with twisted-pair wire; HS-NCM-MFSF for connecting nodes with multi-mode fiber cable to nodes with single-
mode fiber cable. The following equipment may be used with the HS-NCM:
NOTE:
References to V20 HS-NCM indicate hardware assembly HS-NCM-PCA.
References to V30.x and V31.x (or higher) HS-NCM indicate hardware assembly HS-NCM-PCB.
References to V31.x (or higher) indicate hardware assembly HS-NCM-W-2, HS-NCM-WMF-2, HS-NCM-WSF-2 (HS-NCM-PCC)
UL 10th Edition
*
* Power for the HS-NCM for use with 10th Edition panels is provided via the NUP connection on the FACP itself or an external UL/ULC listed power
supply.
UL 8th Edition
Power for the HS-NCM for use with UL 8th Edition panels must be provided by a 24 VDC UL/ULC listed power supply.
NFS2-3030 NFS-3030
NFS2-640 NFS-640
•NFS-320 •NCA
•NCA-2
•DVC-EM
ONYXWorks
•NCD
N16E/N16X
The following revisions
*
of the UL 10th edition panels require a 24 VDC UL/ULC listed power source to power the HS-NCM and cannot be pow-
ered via the panel’s NUP port
:
* The revision and assembly name can be found on the fire panel’s circuit board.
NUP Port connections are still required for communication between the HS-NCM and the fire panel. TX, RX, and GND connections must be used for
NUP connections.
NFS-320
CPU2-640PCB Revision E or older
NFS2-640
CPU2-640PCB Revision E or older
NFS2-3030
CPU2-3030PCC Revision I or older
N16E/N16X
Core/PMB PCB
‡ If TB1 is utilized to power the HS-NCM, a UL Listed, Regulated, Power Limited 24VDC power source is required
•DVC-EM
DVC-EMPCB Revision F or older
•DVC
DVC-PCA All Revisions
•NCA-2
NCA-2PCC Revision I or older
Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier N16E and is the answer not in the manual?

Honeywell Notifier N16E Specifications

General IconGeneral
BrandHoneywell
ModelNotifier N16E
CategoryNetwork Hardware
LanguageEnglish

Summary

Product Overview

Network Communications Module for Wire (HS-NCM-W/W-2)

Network Communications Module for Fiber (HS-NCM-MF, HS-NCM-SF, HS-NCM-MFSF)

Wire and Fiber Network Communications Module (HS-NCM-WMF, HS-NCM-WSF, HS-NCM-WMF-2, HS-NCM-WSF-2)

SFP Adapter Module

HS-NCM Configuration

HS-NCM as a High-Speed Repeater

Installation

Mounting Options

Details various chassis and enclosure mounting locations for HS-NCM modules.

Interconnecting HS-NCM-W/W-2 Modules

Interconnecting Modules

Replacing HS-NCM-W with HS-NCM-W-2

Explains how to replace an HS-NCM-W with an HS-NCM-W-2 using an RJ45 Ethernet cable.

Expanding HS-NCM-W Network with HS-NCM-W-2

Interconnecting Fiber and Wire/Fiber Modules

Mixing Wire & Fiber on One Network

Approved Cables and Distances

HS-NCM-W Applications

Lists approved wiring cables and their maximum allowed distances for HS-NCM-W.

HS-NCM-W-2 Applications

External Power for HS-NCM Applications

Diagnostic Indicators

Supplemental Documentation

Software Disclosure

Related product manuals