THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
45 68-0311—07
4100 Minimum Cool
Setpoint
50° F to 99° F
50° F Both No The user cannot set the temperature below this
level.
4100 Maximum Heat
Setpoint
40° F to 90° F
90° F Both No The user cannot set the temperature above this
level.
4110 Keypad Lockout
Unlocked
Partially Locked
Fully Locked
Unlocked Both No Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any settings.
4120 Residential:
Entry / Exit Remote -
Home Cool Setpoint
Commercial:
Entry / Exit Remote -
Occupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
75° F Both No The thermostat maintains this Cool setting
when the user presses Home / Occupied at the
Entry / Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 130.
4120 Residential:
Entry / Exit Remote -
Home Heat Setpoint
Commercial:
Entry / Exit Remote -
Occupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
70° F Both No The thermostat maintains this Heat setting
when the user presses Home / Occupied at the
Entry / Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 130.
4130 Residential:
Entry / Exit Remote -
Away Cool Setpoint
Commercial:
Entry / Exit Remote -
Unoccupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
78° F Both No The thermostat maintains this Cool setting
when the user presses Away / Unoccupied at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 130.
4130 Residential:
Entry / Exit Remote -
Away Heat Setpoint
Commercial:
Entry / Exit Remote -
Unoccupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
65° F Both No The thermostat maintains this Heat setting
when the user presses Away / Unoccupied at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 130.
4140 Residential:
Entry / Exit Remote -
Vacation Cool
Setpoint
Commercial:
Entry / Exit Remote -
Holiday Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
82° F Both No The thermostat maintains this Cool setting
when the user presses Vacation / Holiday at the
Entry / Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 130.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes