INSTALLATION INSTRUCTIONS
69-2678EFS-03
Alerts and Delta T Diagnostics
with the Prestige® 2.0 IAQ
Thermostat
MOUNTING LOCATIONS
Refer to the guidelines below and Fig. 1–5 for mounting
locations of the Discharge and Return Air Temperature
Sensors.
Discharge Air Temperature
Sensor Mounting Location
1. Mount the Discharge Air Temperature Sensor on
the supply duct in a location where the air is mixed
well. Mount the Discharge Air Temperature Sensor
out of sight of the A-Coil/Heat Exchanger when
possible. See Fig. 1.
2. When possible, mount the Discharge Air
Temperature Sensor upstream of a Steam
Humidifier, a Fan Powered Humidifier or a
Dehumidifier that is ducted to the supply. See Fig.
2–3.
3. If space does not allow a Discharge Air
Temperature Sensor upstream of a Steam
Humidifier or Fan Powered Humidifier, mount the
Discharge Air Temperature Sensor downstream of
the Humidifier. See Fig. 2. When setting the Delta
T Limits (see “Set Delta T Limits” on page 5), be
sure to consider the affect that the humidifier has
on Delta T.
4. If a Bypass Humidifier is installed, the Discharge
Air Temperature Sensor can be mounted
downstream or upstream of the Bypass Humidifier.
Mounting the sensor downstream of the Bypass
Humidifier is the preferred location, because the air
is mixed well. See Fig. 4–5.
Return Air Temperature Sensor
Mounting Location
1. Install the Return Air Temperature Sensor on the
return duct in a location where the air is mixed well.
Mount the Return Air Temperature Sensor
downstream of a Bypass Humidifier, Dehumidifier
or Ventilator. See Fig. 1–5.
Fig. 1.
MOUNT DISCHARGE
SENSOR HERE
M33074
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIFIER
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
VENTILATOR OR
DEHUMIDIFIER
A-COIL
Question and Answer IconNeed help?

Do you have a question about the Honeywell Prestige 2.0 IAQ and is the answer not in the manual?

Honeywell Prestige 2.0 IAQ Specifications

General IconGeneral
Display TypeColor Touchscreen
Wi-Fi ConnectivityYes
RedLINK Wireless TechnologyYes
Humidity ControlYes
ProgrammableYes
IAQ ControlYes
Remote AccessYes
GeofencingYes
AlertsYes
Energy ReportsYes
BacklightYes
Power Source24 VAC
Power MethodHardwired
Voice ControlYes
InstallationProfessional Installation Recommended

Summary

MOUNTING LOCATIONS

Discharge Air Temperature Sensor Mounting Location

Guidelines for mounting the discharge air temperature sensor in the supply duct for optimal air mixing and placement.

Return Air Temperature Sensor Mounting Location

Instructions for installing the return air temperature sensor in the return duct where air is well mixed.

ALERTS AND DIAGNOSTICS

Delta T Diagnostics

Explains how the thermostat tracks system performance using Delta T and alerts users to potential issues.

Before You Set Up Delta T Diagnostics

Provides tips for installing and setting up Delta T Diagnostics, including sensor placement and initial considerations.

Setting up Alerts and Diagnostics

Details the steps to configure the thermostat for alerts and diagnostics, including sensor selection.

Related product manuals