44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170. 
Website: https://www.add-furnace.com/ โทร: 02-888-3472 
Line ID: @add11 e-mail: add028883472@gmail.com 
TROUBLESHOOTING 
 
 
 
❏
 
Energize the module and immediately touch one end of
 
the jumper firmly to the GND terminal on the module. Move 
the  free  end  of  the  jumper  slowly  toward  the  SPARK 
terminal until a spark is established.
 
❏
 
Pull the jumper slowly away from the terminal and note
 
the length of the gap when sparking stops. Check table 
below.
 
 
 
 
 
 
Perform the checkout on page 11 as the first step in 
troubleshooting. Then check the appropriate troubleshoot- 
ing guide (Fig. 14 or 15) and the schematic diagram (Figs. 
16-17) to pinpoint the cause of the problem. If troubleshoot- 
ing  indicates  an  ignition  problem,  see  Ignition  System 
Checks below to isolate and correct the problem.
 
Following troubleshooting, perform the checkout proce- 
dure  (page  11)  again  to  be  sure  system  is  operating 
normally.
 
 
 
IGNITION SYSTEM CHECKS
 
STEP 1: Check ignition cable. 
Make sure:
 
❏
 
Ignition cable does not run in contact with any metal
 
surfaces.
 
❏
 
Ignition cable is no more than 36 in. [0.9 m] long.
 
❏
 
Connections to the ignition module and to the igniter or 
igniter-sensor are clean and tight.
 
❏
 
Ignition cable provides good electrical continuity.
 
STEP 2: Check ignition system grounding. Nuisance shut- 
downs are often caused by a poor or erratic ground. 
❏
 
A common ground, usually supplied by the pilot burner
 
bracket, is required for the module and the pilot burner/ 
igniter-sensor.
 
• 
Check for good metal-to-metal contact between the 
pilot burner bracket and the main burner.
 
• 
Check  the  ground  lead  from  the  GND(BURNER) 
terminal on the module to the pilot burner. Make sure 
connections are clean and tight. If the wire is dam- 
aged or deteriorated, replace it with No. 14-18 gauge, 
moisture-resistant, thermoplastic insulated wire with 
105
 
C [221
 
F] minimum rating.
 
— 
Check the ceramic flame rod insulator for cracks 
or evidence of exposure to extreme heat, which 
can permit leakage to ground. Replace pilot burner/ 
igniter-sensor and provide shield if necessary.
 
— 
If flame rod or bracket are bent out of position, 
restore to correct position.
 
 
STEP 3: Check spark ignition circuit. You will need a short 
jumper wire made from ignition cable or other heavily 
insulated wire. 
❏
 
Close the manual gas valve.
 
❏
 
Disconnect the ignition cable at the SPARK terminal on 
the module.
 
 
 
 
STEP 4: Check pilot and main burner lightoff.
 
❏
 
Set the thermostat to call for heat.
 
❏
 
Watch the pilot burner during the ignition sequence. See 
if:
 
• 
Ignition spark continues after the pilot is lit.
 
• 
The pilot lights and the spark stops, but main burner 
does not light.
 
• 
S8600B,H,M; S8610B,H; S8660D; S8670D only: The 
pilot lights, the spark stops and main burner lights, but 
the system shuts down.
 
❏
 
If so, ensure adequate flame current as follows.
 
• 
Turn off furnace at circuit breaker or fuse box.
 
• 
Clean the flame rod with emery cloth.
 
 
Fig. 13—Examples of unsatisfactory pilot flames.
 
When performing the following steps, do not touch 
stripped end of jumper or SPARK terminal. The 
ignition circuit generates over 10,000 volts and 
electrical shock can result.
 
IMPORTANT
 
1. 
The following service procedures are provided as 
a general guide. Follow appliance manufacturer’s 
service instructions if available.
 
 
2. 
On  lockout  and  retry  models,  meter  readings 
between gas control and ignition module must be 
taken within the trial for ignition period. Once the 
ignition module shuts off, lockout models must be 
reset by setting the thermostat down for at least 
one minute before continuing. On retry models, 
wait for retry or reset at the thermostat.
 
 
3. 
If  any  component  does  not  function  properly, 
make sure it is correctly installed and wired before 
replacing it.
 
 
4. 
The ignition module cannot be repaired. If it mal- 
functions, it must be replaced.
 
 
5. 
Only  trained,  experienced  service  technicians 
should service intermittent pilot systems.
 
No arc or arc less 
than 1/8 in. [3 mm]
 
Check external fuse, if provided. 
Verify power at module input 
terminal.
 
Replace module if fuse and
 
power ok.
 
Arc 1/8 in. [3 mm]
 
or longer.