T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 16
Fig. 32. Program - Sensor.
1.2.3. SENSOR
1. From the menu, use the  and  buttons to 
highlight SENSOR.
2. Press the 
 button to display the sensor selec-
tions.
3. Use the
  and  buttons to select Sensor A or 
B.
4. Press the 
 button to accept the highlighted sen-
sor and display the next option.
Fig. 33. Program - Heat/Cool.
1.2.4. HEAT/COOL
1. From the menu, use the  and  buttons to 
highlight HEAT/COOL.
Default: HEAT
2. Press the 
 button to display the heat and cool 
selections.
3. Use the
  and  buttons to select Heat or Cool.
4. Press the 
 button to accept the highlighted 
selection and display the next option.
Fig. 34. Program - Setback.
1.2.5. SETBACK
The Setback temperature option displays if scheduling is 
enabled (See Fig. 57 on page 24) or the DI Option is set 
to Setback. (See Fig. 60 on page 26).
This is the desired setpoint temperature that you want to 
use during setback mode for this output. For example, if 
your setpoint is 70° F (21° C) and you want the 
temperature to drop 10° F during setback mode, enter 
60° F (16° C) as the setpoint for this output.
1. From the menu, use the
  and  buttons to 
highlight SETBACK.
2. Use the
  and  buttons to increase/decrease 
the desired setpoint temperature.
Default: 60° F (16° C)
Range: -40° to 248° F (-40° to 120° C)
3. Press the 
 button to accept the value and display 
the menu.
1.2.6. Program Next Output (Mod or Relay)
For the next output (Mod or Relay), select the desired 
output from the Program menu (Refer to Fig. 28 on 
page 14).
Go to “1.2.1. SETPOINT” on page 15 to program the next 
output.
When you finish programming the outputs, continue with 
“1.2.7. Exiting Program Mode” on page 17.
MENU
PROGRAM
RELAY 1
SENSOR
SELECT
SENSOR FOR
RELAY 1
SENSOR A
SENSOR B
PROGRAM
 RELAY 1
  SENSOR
M24496
PROGRAM
 RELAY 1
 HEAT/COOL
MENU
PROGRAM
RELAY 1
HEAT/COOL
SELECT
HEAT/COOL
FOR 
RELAY 1
HEAT
COOL
M24497
ENTER
SETBACK
SETPOINT 
FOR RELAY 1
PROGRAM
 RELAY 1
  SETBACK
MENU
PROGRAM
RELAY 1
SETBACK
60
F
o 
M24498