EasyManuals Logo

Honeywell T775B Series Installation Instructions

Honeywell T775B Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
21 62-0254—13
Fig. 46. Setup - Sensors - Sensor B - Throttling Range.
2.2.4.2. THROTTLING RANGE (Sensor B
only)
The throttling range for the modulating high or low limit
positions the setpoint at the end of the throttling range.
For example, with a high limit at Sensor B of 200°F and a
throttling range of 10°F, the modulating output controlling
Sensor A begins to throttle back at 190°F
(88°C), and fully closes at 200°F (93°C). Conversely, the
throttling range for the low limit begins above
the setpoint
in the same manner.
1. From the Limit menu, use the button to highlight
THROT RNG.
2. Use the
and buttons to increase/decrease
the desired value for the Throttling Range.
Default = 0
3. Press the
button to accept the value and return
to the Limit menu.
4. Press the
button to exit the Limit menu.
5. Press the
button to exit the Sensors menu and
return to the Setup menu.
Fig. 47. Setup - Outputs Menu.
2.3. Setting up the Outputs
1. From the Setup menu, use the and buttons
to highlight OUTPUTS.
2. Press the
button to display the Outputs menu.
NOTE: The menus (e.g. the Outputs menu shown
here) can display only those relays that are
defined in Setup (see2.3.2. NBR OF
RELAYS on page 24). For example, if you
configure only two relays, then only two
relays display on the appropriate menus.
The following procedures set up each modulating output
and relay output.
Fig. 48. Setup - Outputs - Modulating Output Menu.
2.3.1. Setting up the Modulating Outputs
1. From the Output menu, use the and but-
tons to highlight the desired modulating output
(MOD 1 or MOD 2).
2. Press the
button to display the selected MOD
menu.
NOTE: Modulating outputs are not available on the
T775A and T775B controller models. If you
are setting up one of these controllers, skip
to 2.3.2. NBR OF RELAYS” on page 24.
Use the remaining procedures, beginning with 2.3.1.1.
TYPE (of output signal) on page 22, to set up each
modulating output. If you have two modulating outputs,
repeat these procedures for each modulating output.
SETUP
SENSORS
SENSOR B
UNITS
CALIBRATE
LABEL
LIMIT
HI LIMIT
THROT RNG
EXIT
SETUP
SENSORS
SENSOR B
ENTER
VALUE FOR
SENSOR B
THROTLING
RANGE
SETUP
SENSORS
SENSOR B
THROT RNG
10
F
o
M24510
SETUP
OUTPUTS
SETUP
OUTPUTS
MOD 1
MOD 2
# RELAYS
OPTIONS
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
M24511
SETUP
OUTPUTS
MOD 1
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT %
INTEGRAL
DERIVATIV
SCHEDULE
HIDE
EXIT
M24512A
All manuals and user guides at all-guides.com
all-guides.com

Other manuals for Honeywell T775B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell T775B Series and is the answer not in the manual?

Honeywell T775B Series Specifications

General IconGeneral
BrandHoneywell
ModelT775B Series
CategoryController
LanguageEnglish

Related product manuals