T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 22
Fig. 49. Setup - Outputs - Mod Out - Type.
2.3.1.1. TYPE (of output signal)
1. From the Mod menu, use the  and  buttons 
to highlight TYPE.
2. Press the 
 button to display the Type selections.
3. Use the 
 and  buttons to highlight the desired 
output type.
Default: 4-20 mA
4. Press the 
 button to accept the selected type and 
return to the Mod menu.
Fig. 50. Setup - Outputs - Mod Out - Minimum Output 
Percentage.
2.3.1.2. MIN OUT %
The minimum output % prevents the output from dropping 
below the value entered. This value can be useful to 
maintain minimum damper position.
Using the time clock or digital input to disable the output 
forces the output to 0%.
1. From the Mod menu, use the
  and  buttons 
to highlight MIN OUT %.
2. Press the 
 button to display the Min Out %.
3. Use the
  and  buttons to increase/decrease 
the desired value from 0% to 100% in 1% incre-
ments.
Default: 0%
Range: 0 to 100%
4. Press the 
 button to accept the percentage and 
return to the Mod menu.
Fig. 51. Setup - Outputs - Mod Out - Integral.
2.3.1.3. INTEGRAL
1. From the Mod menu, use the  and  buttons 
to highlight INTEGRAL.
2. Press the 
 button to display the Integral seconds.
3. Use the
  and  buttons to increase/decrease 
the value from 0 to 3,600 in 10 second increments. 
Default: 400 seconds
Range: 0 to 3,600 seconds
4. Press the 
 button to accept the seconds and 
return to the Mod menu.
NOTES:
1. The Integral time is factory set for 400 
seconds. This is a good middle range and 
should satisfy many applications. The integral 
time can be increased for applications where 
sensed response is slow, and can be 
decreased for applications where sensed 
response is fast (e.g. discharge air control).
2. As a starting point, an optimal integral time for 
discharge air typically ranges from 12 to 200 
seconds. An optimal integral time for room 
control typically ranges from 60 to 2,500 
seconds. The purpose of integral action is to 
reduce or eliminate the offset from setpoint 
during steady state control that is often seen 
in proportional only control.
3. Keep in mind that control is most sensitive to 
throttling range. Adjust the throttling range 
first before any adjustment to integral time. 
Adjust throttling range to be as wide as 
possible to start since this will provide the 
most stable control. Remember that the 
integral will eliminate the steady state error so 
you do not need to have a small throttling 
range to have accurate control. (Integral 
action allows for controlling to a setpoint even 
with a wide throttling range).
SETUP
 OUTPUTS
 MOD 1
  TYPE
SETUP
OUTPUTS
MOD 1
TYPE
SELECT
TYPE FOR
MOD 1
4 - 20 mA
0-10 V
2-10 V
SERIES 90
M24513