T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
21 62-0257—11
Fig. 47. Setup - Outputs - Relay - Schedule.
1.3.5.1. SCHEDULE
This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (see page 15).
When selected, individual outputs default to follow the
schedule.
1. Press the button to display the Schedule values.
2. Use the and buttons to select YES or NO.
Default: YES
3. Press the button to accept the value and return to
the Relay menu.
NOTE: If USE SCHED = YES, then the default is YES.
See “1.3.3.1. USE SCHED” on page 15.
An individual output can be selected to be controlled or
not controlled by the schedule.
If NO is selected, the Setback selection does not appear
in the Program menu for this output.
Fig. 48. Setup - Outputs - Relay - Reset.
1.3.5.2. RESET (Relay Reset)
This selection enables or disables reset for the selected
relay.
IMPORTANT
To use the Reset function of the controller, the
first Loop must be set for Reset.
1. Press the button to display the Reset values.
2. Use the and buttons to select YES or NO.
Default: NO
3. Press the button to accept the value and return to
the Relay menu.
• If you select YES, then the second relay (if available)
displays this Setup option and uses the reset curve
programmed for the first output Loop.
• If you select NO, then No Reset is configured for the
remaining relay output.
Fig. 49. Setup - Outputs - Relay - Reset Runtime.
1.3.5.3. RESET RT (Run Time)
This selection displays only if “Show RT = YES” is
selected during Output Options setup (see page 17).
1. Press the button to display the Reset RT values.
2. Use the and buttons to select YES or NO.
Default: NO
3. Press the button to accept the value and return to
the Relay menu.
Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each of the
first four independent relays. You must do this for
each relay that you want to reset to zero.
SETUP
OUTPUTS
RELAY 9
SCHEDULE
SETUP
OUTPUTS
RELAY 9
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24455
SETUP
OUTPUTS
RELAY 9
RESET
USE
RESET
FOR
RELAY 9
YES
NO
SETUP
OUTPUTS
RELAY 9
RESET
M24456
SETUP
OUTPUTS
RELAY 9
RESET RT
SETUP
OUTPUTS
RELAY 9
RESET RT
RESET
RUN TIME
FOR
RELAY 9
YES
NO
M24457