EasyManua.ls Logo

Honeywell T874 - Page 43

Honeywell T874
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
43 60-2485—8
G1074 Singer no. 02005754; X1 and X2 terminals for
field-added indicator lights; used with
T872D1375.
None
G1082 Singer no. 02005792; X1 and X2 terminals for
field-added indicator lights; used with
T872D1375.
None
G1090 TRADELINE; B and O terminals. Q674G1070
Q672H System: OFF-ON
Fan: NIGHT INT.-DAY CONT.
H1008 Used with T872. None
Q672J System: EM. HT.-AUTO-OFF
Fan: AUTO-ON.
J1005 With EM. HT. LED; used with T872C or D. None
J1013 Westinghouse; heat pump; EM. HT. LED; cool
mode changeover; compressor lockout in
EM. HT.; used with T872G1034.
Y594G1252
J1021 York; heat pump; EM. HT. LED; cool mode
changeover; compressor lockout and auto fan in
EM. HT.; E-W jumper; used with T872G1042,
G1331, G1398.
Y594G1567
J1039 Heat pump; EM. HT. and AUX. HEAT LEDs;
cool mode changeover; compressor lockout and
auto fan in EM. HT.; used with T872G1059.
Y594G1161 Designed for use on General
Electric heat pumps.
J1047 Singer no. 02005699; heat pump; EM. HT. LED;
heat mode changeover.
Q674F1022
J1054 Carrier no. HH93AZ073A; heat pump; EM. HT.
LED; cool mode changeover; compressor
lockout in EM. HT.; used with T872G1075,
G1182, G1307.
Y594G1252 Wiring differences (old=new): C=X.
J1062 Westinghouse; EM. HT. and AUX. HEAT LEDs;
used with T872G1034.
Y594G1252 Wiring differences (old=new):
W=W2.
Q672K System: OFF-HEAT-AUTO-COOL. Fan: None.
K1004 Carrier no. HH93AZ072. Q674E1049 Fan switch does not function.
K1012 Oneida Heater no. 30A0288-01; System: OFF-
WOOD-WOOD/OIL-OIL; used with T872F1175.
T874F1155/
Q674K1026
Q672L System: EM. HT.-HEAT-OFF-COOL.
Fan: ON-AUTO.
L1003 Lennox; heat pump; EM. HT. LED; cool mode
changeover; used with T872R1024.
Y594R1425
L1011 York; heat pump; EM. HT. LED; cool mode
changeover; compressor lockout and auto fan in
EM. HT.; used with T872R1032, R1180, R1297.
Y594R1664
L1029 Lennox no. P-8-11226; heat pump; EM. HT.
LED; V-VR jumper; cool mode changeover;
compressor lockout in EM. HT.; used with
T872R1040.
Y594R1425 Wiring differences (old=new):
V-VR=R, M=Y, Y=W2, F=G, R=O.
L1037 Heat pump; EM. HT. and AUX. HT. LEDs; cool
mode changeover; compressor lockout and auto
fan in EM. HT.; used with T872R1057.
Y594R1763 Wiring differences (old=new): A=T;
designed for used on General
Electric heat pumps.
L1045 Rheem; heat pump; EM. HT. LED; cool mode
changeover; compressor lockout in EM. HT.;
auto fan in EM. HT; used with T872R1065,
R1081, R1107.
Y594R1243
Table 7. Q672-Q674 Subbase Cross Reference.
Model Number Description
Q674 Trade
Replacement
a
Remarks
a
When replacing a T872 Thermostat and Q672 Subbase, always replace both the thermostat and subbase.