EasyManua.ls Logo

Honeywell T874 - Page 59

Honeywell T874
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
59 60-2485—8
G1204 162 Honeywell logo; designed for use on Trane heat pumps;
no H2 anticipation; changeover in cooling mode; used
with Q674J1043 and C815A1005; used in Y594G1161.
Y594G1161
a
Designed for use on Trane
heat pumps.
G1212 155 Obsolete
. Honeywell logo; H2 anticipator factory set at
0.2A; changeover in cooling mode; includes shunt to
bypass H2 anticipator with W3 heat relays; used with
Q674F1238.
Y594G1252
a
G1220 235 Obsolete. Rheem logo; part no. RXMT-C71; changeover
in cooling mode; used with Q674F1238.
Y594G1252
a
G1238 155 Obsolete. Ruud logo; part no. UXMT-C71; changeover
in cooling mode; used with Q674F1238.
Y594G1252
a
G1246 Obsolete. Honeywell logo; changeover in cooling mode.
155 Used with Q674F1212; used in Y594G1195, G1252,
G1369.
Y594G1252
a
170 Used with Q674F1410; used in Y594G1393.
Y594G1393
a
G1261 58, 157 Obsolete. Borg-Warner; used with Q674D1032, F1253. None See subbase description for
replacement information.
G1279 58, 157 Obsolete
. Bryant logo; used with Q674D1032, F1253. None See subbase description for
replacement information.
G1287 58, 157 Obsolete
. Wesco logo; used with Q674D1032, F1253. None See subbase description for
replacement information.
G1295 58 Obsolete
. York logo; part no. 2TH11702724A; used with
Q674D1032.
T874D1165/
Q674D1040
Wiring differences (old=new):
Y=Y2, O=Y1, W=W2; jumper
W1-Y2.
G1345 160 Obsolete
. York logo; part no. 2TH11702624A; °C
scaleplate; used with Q674J1027.
Y594G1575
a
G1352 73 Obsolete. Command-Aire logo; 12°F differential
between H1 and H2 for night setback; used with
Q674C1066.
Y594H1012
a
Wiring differences (old=new):
Y1=O, Y2=Y, L=R, R=none; R-
L jumper required; no night
setback.
T8600D1004
(programmable)
Wiring differences (old=new):
Y1=O, Y2=Y, L=RH; RC-RH
jumper required; includes
night setback.
G1378 79 Obsolete
. Mammoth logo; H2 anticipator factory set at
0.8A; 12°F differential between H1 and H2 for night
setback; °F/°C scaleplate; used with Q674C1124; used
in Y594G1294.
Y594H1012
a
Wiring differences (old=new):
R1=none, R2=L; R-L jumper
required; no night setback.
T8090A1007/
Q682A1038
a
(programmable)
Includes night setback; W-Y
jumper required.
G1402 129 Obsolete
. York part no. 2TH11702824A; meets DoD
specifications; used with Q674L1363.
Y594R1425
a
Wiring differences (old=new):
W=W2, X=E, B=X; jumper
Y-W1.
G1410 155 Obsolete
. Borg-Warner multi-logo; part
no. 6TH11703024A; used with Q674F1311.
T874G1246
a
or
Y594G1252
a
G1428 160 Obsolete. Borg-Warner multi-logo; part no.
6TH11702424A; used with Q674J1027; used in
Y594G1229.
Y594G1567
a
G1436 58 Obsolete. Borg-Warner multi-logo; part no.
6TH11702724A.
T874D1165/
Q674D1040
Wiring differences (old=new):
Y=Y2, O=Y1, W=W2; jumper
W1-Y2.
Table 8. T874 Cross Reference.
Model
Number
Fig.
No. Description
Trade Model
Replacement Remarks
a
Both the thermostat and subbase must be replaced.