EasyManua.ls Logo

Honeywell TH6100AF2004 - Floor Temperature Sensor Installation; Recommended Floor Temperatures Settings

Honeywell TH6100AF2004
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
Floor temperature sensor installation
T6 Pro Hydronic thermostat is compatible
with the following 10K ohm floor temperature
sensors: AQ12C20 and AC11201.
The floor temperature sensor needs to be
installed mid way between the piping to
ensure proper temperature reading (not over
or right next to piping). Example: For a 12
pipe spacing install the sensor 6” away from
the piping and ensure the sensor is vertically
centered.
We recommend installing the floor
temperature sensor inside of min. 0.5
PEX pipe. This simplifies future sensor
replacement, if required.
In a small room, position the sensor in the
center of the floor. In larger rooms, ensure the
sensor is at least 7 feet from the wall.
Recommended floor temperatures
settings
Recommended maximum floor temperature
is 90 °F (32 °C) for most floor covering types
except wood. Suggested maximum floor
temperature for wood floor is 85 °F (29.5 °C).
Freeze protection temperature for garages and
basements is suggested to be set between
4145 °F (57.2 °C).
Floor sensor conduit position in a slab
FLOOR SENSOR
CONDUIT
HEATING PIPE
S
SLAB

Related product manuals