WIRING
Humidier 69-2413EF—09
22
Honeywell HumidPRO
TM
Frost Index
Installer System Test/Checkout
Outdoor Temp
-10°F 0°F 10°F 20°F 30°F 40°F
Frost Index
1 10 10 10 10 11 11 17 17 25 25 35 36
2 10 10 10 10 15 15 21 21 29 29 35 39
3 10 10 14 14 19 19 26 26 34 34 35 46
4 15 15 19 19 25 25 32 32 35 39 35 52
5 21 21 26 26 32 32 35 38 35 48 35 58
6 29 29 34 34 35 39 35 48 35 56 35 60
7 35 39 35 46 35 52 35 58 35 60 35 60
8* 35 56 35 60 35 60 35 60 35 60 35 60
9 35 60 35 60 35 60 35 60 35 60 35 60
10 35 60 35 60 35 60 35 60 35 60 35 60
*Black Numbers show highest humidity allowed when Default RH% (35%) is Selected.
Note: Smaller grey numbers show highest humidity allowed when Maximum RH% (60%) is selected.
Press p / q to turn system on/off.
Press NEXT to advance to next test.
Press DONE to terminate system test.
To begin, press and hold the p and q buttons until the display changes.
Function Number
Setting
Number Description
10 System Test
0 OFF
1 ON
20 View Outdoor Temperature Shows Outdoor Temperature
10
0
M29388A
Test number System status
NOTE: Most humidiers require airow in the system to operate. Make sure to turn on the system fan when
testing humidier operation.
H6062 Specications
Humidity Ranges:
Humidify:
Default: 10% to 60%
Total Range Available: 10% to 90%
Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)