Funnel or floor drain. Refer to governing
codes for drain pipe size and maximum
temperature requirements.
6 in.
8 in.
1
Choose a location for TrueSTEAM and the
remote duct nozzle.
It should have access for:
• Remotehoseinstallation.Steamhose
must be installed with 2 in./ft. pitch on a
continuous uphill slope.
• Drain.Allowacontinuousdownslopetothe
drain.
• Coldwaterline.
• Electricalcircuitratedtoyourhumidifier
(see circuit ratings on page 5).
Remote mount installation
Maximum 3 ft.
2 in./ft. uphill
1/2 in.
minimum
diameter
Water in
elbow
ThiskitisusedwiththeHoneywellTrueSTEAM
TM
humidifier to allow the humidifier to be
mountedupto20feetawayfromtheduct.Thiskitincludeseverythingneededtocompletethe
installation,includinginsulatedsteamhosethatwillensuremaximumefficiency.
Followtheseinstallationinstructionscarefullyfortrouble-freeoperation.
Mostoperationproblemsarecausedbyimproperhoseinstallation.Alwaysensureanuphillflow
when installing the remote hose, and avoid kinks, sharp turns, or low spots that could restrict
the flow of steam into the injection nozzle or condensation back into the humidifier.
If the remote hose cannot be installed with an upward pitch of 2 in./ft., a wetted drip tee must
be installed. Failure to do so can result in back pressure on TrueSTEAM, which can lead to duct
nozzle water spitting or leaking gasket. Remote hose must be supported to prevent sagging or
low spots.