EasyManua.ls Logo

Honeywell TrueSTEAM HM509 - Effect of Ventilation on Indoor Humidity Levels; How Air Temperature Affects Relative Humidity; Consequences of Undersizing Humidifiers; Sizing Considerations Summary

Honeywell TrueSTEAM HM509
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TrueSTEAM Humidification System
7 69-2276EFS—01
Remote mount installation Remote mount installation
M24770
Cuta1-3/4in.diameterducthole,installtheprovided
gasket, and slide the remote nozzle up into the duct.
Secureremotenozzletoductusing#8self-drilling
sheet metal screws (4).
6
Run remote hose from
the humidifier to the duct
nozzle location. Up to 20
ft. of hose can be used.
7
Ifmountingremotelyrequiresrunning
hose through structural barriers (ie. wall
or ceiling), cut at least a hole and slide
hose through. The insulated hose is
2-1/8in.diameter.
Seal off unconditioned space with a
grommet (not provided) or caulk.
8
Minimum 3 in. clearance
required from nozzle outlet to
duct wall.
69-2276EFS_A.indd 7 9/25/2008 9:26:52 AM

Other manuals for Honeywell TrueSTEAM HM509

Related product manuals