Honeywell TrueSTEAM Series - VisionPRO IAQ Wiring Configuration

Honeywell TrueSTEAM Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
WIrING
— In VisionPRO IAQ, this is setup function 0374
Option 1 forces the fan on. This energizes system G when the HUM terminals energize from a humidity
demand
• Option 0 or 2 waits for the system to energize G before allowing HUM terminals to energize
Because the thermostat is enforcing the fan, you do not need to power monitor or activate fan from
TrueSTEAM – the control does it for you.
On TrueSTEAM, set DIP-4 up. Wire only HUM-HUM terminals of TrueSTEAM to HUM-HUM terminals of the
Equipment Interface Module of VisionPRO IAQ.
Wiring TrueSTEAM with VisionPRO IAQ