InstalltoFitYourApplication(continued)
C
Exhaust and Supply in the Return
Whenusingthisapplicationmakesurethatthereisaminimumof6feetbetweenthefreshairand
exhaustairconnectionsoftheERV/HRVunitinthereturnairduct.SupplyairfromtheERV/HRVunit
mustbeatleast3feetfromtheforcedairsystem.Thesedistancescanbedifferentfromoneregionto
another;youshouldcheckwithyourlocalcodeortheforcedairsystem’smanufacturer.
NOTE: Forminimumdistancebetweenreturnandforcedairsystem,checkwithyourlocalbuilding
codesandforcedairsystemmanufacturer.
NOTE: Freshairmustalwaysbedown-streamfromtheexhaustairinthereturnairductoftheforced
airsystem.
NOTE: Furnaceblowerisrequiredtooperatewhenventilationisrequired.Setthefurnaceblowertorun
continuously,orinterlockelectrically(lowvoltage).
TO LIVING SPACE
HRV / ERV
FORCED AIR
SYSTEM
3 FEET
6 FEET
6 FEET
18 INCHES
M28985
ERV/HRVVentilationSystems69-2480EF—01