WEBVISION™
95-7769—01 128
FCU Status Mode X X X Disabled
Cool
Heat
Pressurize
Depressurize
Manual Mode
Factory Test Mode
Floating Out of Sync
Fan Switch Off
Startup Wait
Output Position 0 X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Output Position 1 X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Primary Heat Output X X X Units=%
Precision=1
Min=-163.8
Max=163.8
RO LED X X X Default
Occupied
Unoccupied
Bypass
Standby
Reheat Active X X X Default
Off
Low
Medium
High
On
Reset Bypass Time X X X Units=min
Precision=0
Min=0.0
Max=65535.0
Scheduled Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Secondary Heat Output X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Sensor Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Space Temperature X X X Units=ºC
Precision=1
Min=-273.2
Max=327.7
Terminal Load X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Table 79. FCU Application of Points (Continued)
Point name Graphics Alarms Trends Commandable Internal Use Valid Values