EasyManua.ls Logo

Honeywell WebVision - Page 137

Honeywell WebVision
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WEBVISION™
137 95-7769—01
Analog In 3 X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Analog In 4 X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Analog In 5 X X X Units=null
Precision=0
Min=-32768.0
Max=32767.0
Analog In 6 X X X Units=null
Precision=0
Min=-32768.0
Max=32767.0
Digital In 1 X X X False or True
Digital In 2 X X X False or True
Digital In 3 X X X False or True
Digital In 4 X X X False or True
Digital Out 1 X X X Off or On
Digital Out 2 X X X Off or On
Digital Out 3 X X X Off or On
Digital Out 4 X X X Off or On
Digital Out 5 X X X Off or On
Digital Out 6 X X X Off or On
Digital Out 7 X X X Off or On
Digital Out 8 X X X Off or On
Mode X X X Startup Wait
Heat
Cool
Off
Disabled
Emergency Heat
Smoke Emergency
Freeze Protect
Manual
Factory Test
Fan Only
Table 83. RIO Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values