WEBVISION™
147 95-7769—01
Unoccupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Occupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State X Default
Occupied
Unoccupied
Bypass
Standby
Next State X Default
Occupied
Unoccupied
Bypass
Standby
Time To Next State X Units=min
Precision=0
Min=0.0
Max=65535.0
DLC Shed X dlNoDlcShed
dlMinDlcShed
Communication Failed X False or True
Frost Protect X False or True
Invalid Config X False or True
Invalid Setpoint X False or True
Node Disabled X False or True
Sensor Failed X False or True
Smoke Emergency X False or True
Table 87. VAV II Application of Points (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values