4 211 793 / 00
7
Subject to modication
9
│
Checklist in case of faults
Operator terminal BG02
Observation Ventilation unit Cause Remedy
The LED control lamp
does not light up.
Not in operation.
Ventilation unit is not con-
nected to the mains.
Plug in the ventilation unit.
Ventilation unit is not swit-
ched on.
Turn on the mains switch
of the ventilation unit.
Microfuse of the ventilation
unit is defective.
Phone Hoval Customer
Service.
AirowratePUSH&
TURN button is set to 0.
Set the PUSH & TURN
button to the required basic
ventilation setting.
The operator terminal is not
connected.
Check that the connecting
cable is plugged into the
operator terminal and the
ventilationunit(RJ45).
The operator terminal is
defective.
Phone Hoval Customer
Service.
The LED control lamp
lights up orange.
In operation.
Supplyair/extractairlters
are soiled.
Insertnewlters.
Samefaultwithnewlters.
Phone Hoval Customer
Service.
The LED control lamp
lights up red.
Not in operation.
Group alarm, ventilation
unit.
Phone Hoval Customer
Service.
Ifthecontrollampashesasdescribedbelow,theunitisinoperatingmode"Party"(notafault).
Observation Ventilation unit Cause Remedy
The LED control lamp
ashesgreen.
In operation.
Unit is in Party mode (air
owrate100%).
Party button has been
pressed.
To exit the Party function,
press the Party button for 2
seconds.