26
13a)________On ice flakers with the solenoid valve interlocked with the condensing unit, the
compressor will pump down and cycle off once the compressor reaches the low pressure switch
cut-out point.
14)________ Ice flaker is pumped down, (Solenoid valve is de-energized) drive motor & water
pump continue to run until the off delay cycle opens. Field Adjustable between 1-30 minutes,
normally set at approximately 5-10 minutes.
15)________ Electronic overload set point is factory set to trip within seconds when the motor
reaches an overloaded condition.
16)________ Ice maker is adjusted and producing dry, flakes of ice.
17)________ Water is NOT dripping into the bin. If it is, locate the dripping point and correct
it. (i.e.: distribution pan overflowing, water recovery trough overflowing, or distribution tubes
broken or misaligned.)