HP MODULAR PDU SPECIFICATIONS
Mechanical Dimensions (WxHxD) 17.5 x 1.62 x 5.6 in/44.45 x 4.11 x 14.22 cm
Unit Weight 18 lb/8.16 kg
Shipping Dimensions (WxHxD) 21.5 x 12.25 x 13.0 in/54.61 x 31.12 x 33.02 cm
Shipping Weight 20.2 lb/9.16 kg
Operating Temperature
50° to 122°F/10° to 50°C
Operating Relative Humidity (%) 10% to 90%
Operating Elevation 0 to 10,000 ft/0 to 3048 m
Storage Temperature –4° to 140°F/–20° to 60°C
Storage Relative Humidity (%) 5% to 95%
Storage Elevation 0 to 30,000 ft/0 to 9144 m
Conformance Standards UL, CUL, CE, NOM, D - 16A and 40A models
UL, CUL, NOM – 24A High and Low voltage models
CE, D - 32A model
Kit Contents
24-40A Modular PDUs ship with x1 Control Unit and x4 Extension Bars
16A Modular PDU ship with x1 Control Unit and x2 Extension Bars
All models ship with:
0U/1U Mounting brackets/hardware for Control Unit
Mounting brackets for Extension Bars
Cord Retention bracket for the Control Unit
Tie wraps
Install Card
High voltage models ship with two 10A, IEC320 -C14 to IEC 320 -C13 jumper cables, each 4.5ft/1.37m long. In
addition, the 16A model ships with one 16A, IEC 320-C19 to IEC 320-C20 jumper cord, 8.2ft/2.5m long.