EasyManuals Logo

HP 6268B Operating And Service Manual

HP 6268B
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
f.
Reset
crowbar
by
returning
OVERVOLTAGE
ADJUST
control
to
its
maximum
clockwise
position
and
turning
off
the
supply.
On
turning
the
supply
back
on,
the
voltage
should
be
the
same
value
as
was
set
in
step
(d).
g.
To
check
the
constant
current
circuit,
first
turn
off
the
supply,
connect
a
short
across
the
output
bus
bars
(see
Figure
3-2),
and
turn
it
back
on.
h.
Adjust
COARSE
and
FINE
CURRENT
controls
(7)
until
ammeter
(8)
indicates
desired
output
current
or
current
limit.
(The
VOLTAGE
controls
must
be
set
for
a
greater-than-zero
output
to
obtain
the
output
current
programmed.)
i.
Turn
off
the
supply,
remove
the
short
from
its
out¬
put,
and
read
the
remainder
of
these
operating
instructions
before
connecting
the
supply
to
an
actual
load.
3-3
OPERATING
MODES
3-4
This
power
supply
is
designed
so
that
its
mode
of
operation
can
be
selected
by
making
strapping
connections
between
terminals
on
its
rear
panel.
The
following
para¬
graphs
first
describe
normal
operation
using
the
normal
strapping
pattern
as
it
is
connected
at
the
factory.
Later
paragraphs
cover
some
optional
operating
modes
including
remote
voltage
sensing,
remote
programming,
and
some
methods
of
operating
these
power
supplies
in
combinations
of
two
or
three.
3-5
The
DC
Power
Supply
Handbook,
Application
Note
90A,
is
a
useful
source
of
additional
information
on
using
regulated
power
supplies
effectively.
This
138-page
handbook
includes
chapters
on
operating
principles,
ac
and
load
connections,
optional
operating
modes,
and
performance
measurements
and
is
available
at
no
charge
from
your
local
HP
sales
office.
The
address
of
your
local
sales
office
can
be
found
in
the
back
of
this
manual.
3-6
NORMAL
OPERATING
MODE
3-7
This
power
supply
was
shipped
with
the
proper
rear
panel
strapping
connections
made
for
constant-voltage/
constant-current
operation
with
local
sensing
and
local
programming.
This
strapping
pattern
is
illustrated
in
Figure
3-2.
By
means
of
the
front
panel
voltage
and
current
controls,
the
operator
selects
either
a
constant-voltage
or
a
constant-current
output.
Whether
the
supply
functions
in
the
constant-voltage
or
the
constant-current
mode
depends
on
the
settings
of
the
voltage
and
current
controls
and
on
the
resistance
of
the
output
load.
For
values
of
load
resis¬
tance
greater
than
a
critical
crossover
value
equal
to
the
voltage
setting
divided
by
the
current
setting,
the
supply
operates
in
the
constant-voltage
mode.
With
a
load
resis¬
tance
smaller
than
this
critical
value,
it
operates
in
the
constant-current
mode.
The
transition
occurs
automati¬
cally;
no
switches
need
to
be
operated
or
connections
changed.
EXT.
CROWBAR
TRIGGER
'
+
-
'
AI
A2
A3
A4
A5
A6
A7
A8
fS
-S
A9
i
IE
3E
p
0
r
t-i
5
-OUT
-0
+
OUT
Figure
3-2.
Normal
Strapping
Pattern
3-8
Constant
Voltage
Operation
3-9
To
adjust
the
supply
for
constant
voltage
operation:
a.
Turn
on
supply
and,
with
output
terminals
open,
adjust
the
VOLTAGE
controls
for
the
desired
output
voltage.
Then
turn
power
off.
b.
Connect
a
short
across
the
rear
panel
output
terminals,
restore
power,
and
adjust
the
CURRENT
controls
for
the
desired
maximum
output
current.
Then
remove
the
short.
If
a
load
change
causes
this
current
limit
to
be
exceeded,
the
supply
automatically
crosses
over
to
constant
current
operation
at
this
preset
current
limit
and
the
output
voltage
drops
proportionately.
In
setting
the
current
limit,
make
an
adequate
allowance
for
high
peak
currents
that
could
cause
unwanted
crossover.
(Refer
to
paragraph
3-77.)
3-10
Constant
Current
Operation
3-11
To
adjust
the
supply
for
constant
current
operation;
a.
Connect
a
short
across
the
rear
output
terminals,
turn
the
power
on,
and
adjust
the
CURRENT
controls
for
the
desired
output
current.
b.
Open
the
output
terminals
and
adjust
the
VOLTAGE
controls
for
the
desired
maximum
output
voltage.
If
a
load
change
causes
this
voltage
limit
to
be
exceeded,
the
supply
automatically
crosses
over
to
constant
voltage
opera¬
tion
at
this
preset
voltage
limit
and
the
output
current
drops
proportionately.
In
setting
the
voltage
limit,
make
an
adequate
allowance
for
high
peak
voltages
that
could
cause
unwanted
crossover.
(Refer
to
paragraph
3-77.)
3-12
Overvoltage
Trip
Point
Adjustment
3-13
The
crowbar
trip
voltage
is
adjusted
by
using
the
screwdriver
control
on
the
front
panel.
The
approximate
trip
voltage
ranges
are
listed
in
Table
1
-1.
When
the
crowbar
trips,
an
SCR
shorts
the
output
and
the
amber
OVER¬
VOLTAGE
indicator
on
the
front
panel
lights.
Rotating
the
control
clockwise
sets
the
trip
voltage
higher.
(It
is
set
to
maximum
at
the
factory.)
Paragraph
5
108
contains
instruc¬
tions
for
completely
disabling
the
crowbar,
if
this
is
desired.

Other manuals for HP 6268B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP 6268B and is the answer not in the manual?

HP 6268B Specifications

General IconGeneral
BrandHP
Model6268B
CategoryPower Supply
LanguageEnglish

Related product manuals