Hardware options installation 62
10.
Connect the power cable from the drive to the system board.
11. Connect the SATA cable from the drive to the system board.
12. Install the fan cage.
13. Install the air baffle.
14. For tower models, do the following:
a. Install the access panel (on page 23).
b. Return the server to an upright position.
15. For rack models, do the following:
a. Install the rack bezel (on page 22).
b. Install the access panel (on page 23).
c. Slide the server back into the rack.
16. Connect each power cord to the server.
17. Connect each power cord to the power source.
18. Press the Power On/Standby button.
The server exits standby mode and applies full power to the system. The system power LED changes
from amber to green.
19. Do one of the following:
o For tower models, install the bezel.
o For rack models, if removed, install the security bezel (on page 45).
Redundant power supply option
IMPORTANT: The DC power supply unit must only be installed by a qualified technician.
•
The 14 AWG green or yellow wire must be fastened to the metal enclosure with a screw and
a spring or star washer.
• When installing the DC power supply unit, the ground wire must be connected before the
positive or negative leads.