EasyManua.ls Logo

HP T1000 - Output Tolerance Specifications; Output Feature Specifications; Battery Specifications; Battery Runtime

HP T1000
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications 33
Configuration setting (VAC) Available nominal output voltage (VAC)
230 230
240 240
Output tolerance specifications
Source of power Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
Battery power ±5% of nominal output voltage rating
Output feature specifications
Feature Specification
Online efficiency 94% nominal input voltage
Voltage wave shape Sine wave; 5% THD with typical PFC load; 15-20% THD on battery
Surge suppression High-energy 6500 A peak
Noise filtering MOVs and line filter for normal and common mode use
Battery specifications
Feature Specification
Type 12 V, 9 AH, sealed, maintenance-free, rechargeable, lead-acid battery.
Charging
Complete charge takes no more than 24 hours. After approximately 4 hours, the batteries
reach 90% charge at default nominal utility voltage and no load.
Battery runtime
Load, percent Load, watts Estimated battery runtime at 100% battery charge
20 100 45 minutes
50 250 15 minutes
80 400 6 minutes
100 500 4 minutes
Environmental specifications
Feature Specification
Operating temperature 0°C to 40°C (32°F to 104°F)
Nonoperating temperature -15°C to 50°C (5°F to 122°F)
Relative humidity 0% to 95%; noncondensing