Shenzhen Hpmont Technology Co., Ltd. Chapter 8 Troubleshooting and Maintenance
HD09 Series User Manual V1.1 -57-
Fault Fault reasons Counter-measures
E0019
Motor overload
Improper setting of V/f curve
Mains supply voltage is too low
Normal motor runs for a long time
with heavy load at low speed
Motor runs with blocked torque or
load is too heavy
Adjust thesetting of V/f curve (F09.01 -
F09.06)
Check the power input
Please use special motor
Please check the load and mechanical
transmission devices
E0021
Access fault of
Control board
EEPROM
Memory circuit fault of control
board EEPROM
Please contact the supplier for
repairing
E0024
Fault of external
equipment
Fault terminal of external
equipment operates
Please check external equipment
E0028
SCI communication
time-out
Connection fault of
communication cable
Disconnected or not well
connected
Please check the connection
E0029
SCI communication
error
Connection fault of
communication cable
Disconnected or not well
connected
Communication setting error
Communication data error
Please check the connection
Please check the connection
Please correctly set the
communication format (F17.00), and
the baud rate (F17.01)
Note:
If E0028 or E0029 are displayed on the keypad, there is no need to stop the inverter.