NetCol8000-A(045, 055, 060, 090, 120) In-room
Air Cooled Smart Cooling Product
Quick Guide
Issue: 05
Part Number: 31500BLY
Date: 2021-10-20
Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol500-A060 and is the answer not in the manual?

Summary

Onsite Preparation

Refrigerant R410 A

Details about R410A refrigerant, including authenticity verification and pressure mapping.

Installing the Indoor Unit

Installing the Outdoor Unit

Installation Scenarios

Illustrates horizontal, vertical, and compact installation layouts and spacing requirements.

Checking Nitrogen Discharge at Outdoor Unit Needle Valves

Procedure to check nitrogen discharge at outdoor unit needle valves for different models.

Connecting Refrigerant Pipes

Laying Engineering Pipes

Guidance on laying refrigerant pipes, including material considerations and welding precautions.

Installing Cables

Connecting the Indoor Unit Power Cable

Instructions for connecting the power cable to the indoor unit.

Connecting the Outdoor Unit Power Cable

Guide for connecting the power cable to the outdoor unit.

Leak Checking, Vacuuming, and Precharging Refrigerant

Leak Checking

Procedure for leak checking the system using nitrogen pressure.

Vacuuming

Steps for vacuuming the system to remove moisture and air.

Precharging Refrigerant

Guide for precharging the system with refrigerant R410A.

Commissioning

Power-On

Steps and precautions for powering on the smart cooling product for the first time.

Startup Process

Detailed flowcharts for the initial startup and wizard configuration process.

Summary

Onsite Preparation

Refrigerant R410 A

Details about R410A refrigerant, including authenticity verification and pressure mapping.

Installing the Indoor Unit

Installing the Outdoor Unit

Installation Scenarios

Illustrates horizontal, vertical, and compact installation layouts and spacing requirements.

Checking Nitrogen Discharge at Outdoor Unit Needle Valves

Procedure to check nitrogen discharge at outdoor unit needle valves for different models.

Connecting Refrigerant Pipes

Laying Engineering Pipes

Guidance on laying refrigerant pipes, including material considerations and welding precautions.

Installing Cables

Connecting the Indoor Unit Power Cable

Instructions for connecting the power cable to the indoor unit.

Connecting the Outdoor Unit Power Cable

Guide for connecting the power cable to the outdoor unit.

Leak Checking, Vacuuming, and Precharging Refrigerant

Leak Checking

Procedure for leak checking the system using nitrogen pressure.

Vacuuming

Steps for vacuuming the system to remove moisture and air.

Precharging Refrigerant

Guide for precharging the system with refrigerant R410A.

Commissioning

Power-On

Steps and precautions for powering on the smart cooling product for the first time.

Startup Process

Detailed flowcharts for the initial startup and wizard configuration process.

Huawei NetCol500-A060 Specifications

General IconGeneral
ModelNetCol500-A060
Cooling Capacity60 kW
RefrigerantR410A
Operating Temperature Range (Cooling)18°C to 45°C
IP RatingIP20
Sound Pressure Level65 dB(A)