EasyManua.ls Logo

Huawei OptiX OSN 8800 T16 - Page 56

Huawei OptiX OSN 8800 T16
139 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
4 Installing Power Cables Between the DPD63-8-8 PDU and PDF
Both NEG(-) and RTN(+) terminal pairs must be connected or disconnected.
Installing Power Cables
d
Connect external power cables (blue) to the NEG(-) input terminals and BGND cables (black) to RTN(+) input terminals.
Correctly connect two-hole OT terminals to the copper fittings. Ensure that the protruding sides of the OT terminals facing
outward.
Connect external power cables (blue) to the NEG(-) input terminals and BGND cables (black) to RTN(+) input
terminals. Ensure that the fluted sides of the cord end terminals face outwards.
Power cable connections when copper fittings are not installed
A1
(-)
A2
(-)
A3
(-)
A4
(-)
B1
(-)
B2
(-)
B3
(-)
B4
(-)
A1
(+)
A2
(+)
A3
(+)
A4
(+)
B1
(+)
B2
(+)
B3
(+)
B4
(+)
-48 V power cables (blue)
NEG(-)
BGND cables (black)
RTN(+)
-48 V power cables (blue)
NEG(-)
M5
2.04 ± 0.20 N.M
2# screwdriver
M6
3.06 ± 0.30 N.M
3# screwdriver
Installing cord end terminals when copper fittings are not installed
Installing cord end terminals when copper fittings are installed

Related product manuals