60
7 Subrack Power Cable Connections
1 x T64 Subrack + 4 x 6800 Subracks
b
PDU
T64
6800
6800
Subrack 2
a3(+)
b3(+)
b3(-)
a3(-)
Subrack 1
Power cable connections are the same on
the front and rear sides. This page
describes only the front-side power cable
connections.
NOTE
Subrack 1
Subrack 2
Subrack 3
a1
(-)
a2
(-)
a3
(-)
a4
(-)
b1
(-)
b2
(-)
b3
(-)
b4
(-)
b1
(+)
b3
(+)
b4
(+)
b2
(+)
a1
(+)
a3
(+)
a4
(+)
a2
(+)
DPD63-8-8 PDU
a1
(+)
a1
(-)
a2
(+)
a2
(-)
b1
(+)
b1
(-)
b2
(+)
b2
(-)
DC PDU Subrack
No.
Circuit
Breaker
No.
Circuit
Breaker
Current
SW1A,
SW2A,
SW1B,
SW2B
TN51PDU: 60
A
DPD63-8-8
PDU: 63 A
1
SW3A,
SW3B
TN51PDU: 30
A
DPD63-8-8
PDU: 32 A
2
SW4A,
SW4B
TN51PDU: 30
A
DPD63-8-8
PDU: 32 A
3
Mapping between Subracks and
DC PDUs
For the T64 Enhanced subrack, the PIU boards installed back-to-back are in mutual backup.
For the T64 General, T32, and T16 subracks, PIU boards on the left and right sides are in
mutual backup.
For the universal platform subracks, the PIU boards are installed on the right side and the
upper and lower PIU boards are in mutual backup.
For details of the backup relationships between PIU boards, see the "Power Redundancy"
section.
CAUTION
Subrack 3
a4(+)
a4(-)
b4(+)
b4(-)
TN51PDU
a1
(-)
a2
(-)
a3
(-)
a4
(-)
a1
(+)
a3
(+)
a4
(+)
a2
(+)
b1
(-)
b2
(-)
b3
(-)
b4
(-)
b1
(+)
b3
(+)
b4
(+)
b2
(+)