Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Causes Suggestions
2034 Grid
Overvolt
age
Major Cause ID = 1
The grid voltage exceeds the
upper threshold or the
overvoltage duration exceeds the
time that triggers high voltage
ride-through (HVRT).
1. Check whether the grid
connection voltage exceeds
the upper threshold. If yes,
contact the local power
operator.
2. If you have
conrmed that
the grid connection voltage
exceeds the upper
threshold and have
obtained the consent of
the local power operator,
modify the overvoltage
protection threshold.
3. Check whether the peak
grid voltage exceeds the
upper threshold.
2035 Grid
Volt.
Imbalan
ce
Major Cause ID = 1
The dierence between grid
phase voltages exceeds the upper
threshold.
1. Check that the grid voltage
is within the normal range.
2. Check that the AC output
power cable is correctly
connected. If the AC output
power cable is correctly
connected, yet the alarm
persists and
aects the
energy yield of the PV
plant, contact the local
power operator.