Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Causes Suggestions
2034 Grid
Overvolt
age
Major Cause ID = 1
The grid voltage exceeds the
upper threshold or the
overvoltage duration exceeds the
time that triggers high voltage
ride-through (HVRT).
1. Check whether the grid
connection voltage exceeds
the upper threshold. If yes,
contact the local power
operator.
2. If you have
conrmed that
the grid connection voltage
exceeds the upper
threshold and have
obtained the consent of
the local power operator,
modify the overvoltage
protection threshold.
3. Check whether the peak
grid voltage exceeds the
upper threshold.
2035 Grid
Volt.
Imbalan
ce
Major Cause ID = 1
The dierence between grid
phase voltages exceeds the upper
threshold.
1. Check that the grid voltage
is within the normal range.
2. Check that the AC output
power cable is correctly
connected. If the AC output
power cable is correctly
connected, yet the alarm
persists and
aects the
energy yield of the PV
plant, contact the local
power operator.
SUN2000-(75KTL, 100KTL, 110KTL, 125KTL) Series
User Manual 8 Maintenance
Issue 11 (2021-11-10) Copyright © Huawei Technologies Co., Ltd. 115

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-100KTL-M0 and is the answer not in the manual?

Huawei SUN2000-100KTL-M0 Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-100KTL-M0
CategoryInverter
LanguageEnglish

Related product manuals