EasyManuals Logo

Huawei UPS2000-A-1KTTS User Manual

Huawei UPS2000-A-1KTTS
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
6 Operations
6.1 Checking Before Power-On
AC power cable colors comply with local regulations.
The input and output are not short-circuited.
Cables and terminals are securely connected.
Battery cables and terminals are correctly connected, and voltages comply
with industry standards.
The UPS is properly connected to battery strings.
Power cables and signal cables are correctly labeled.
Cables are neatly routed and securely bound according to requirements.
The equipment is installed and cables are routed in ways that facilitate
modication, capacity expansion, and maintenance.
The equipment is properly grounded.
The voltage dierence between the neutral wire and the ground cable is less
than 5 V AC.
The input voltage range for the mains to start the UPS is 175–270 V AC. The
input voltage range for batteries to start the UPS is (Number of batteries x
10.8 V DC) to (Number of batteries x 14 V DC).
UPS2000-A-(1 kVA-3 kVA)
User Manual 6 Operations
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 74

Other manuals for Huawei UPS2000-A-1KTTS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A-1KTTS and is the answer not in the manual?

Huawei UPS2000-A-1KTTS Specifications

General IconGeneral
ModelUPS2000-A-1KTTS
CategoryUPS
Input Frequency50/60 Hz
Output Frequency50/60 Hz
Output WaveformSine Wave
TopologyLine-Interactive
Operating Temperature0°C to 40°C
Storage Temperature-15°C to 45°C
Humidity0% to 95% (non-condensing)
Capacity1 kVA
Input Voltage230V
Input Frequency Range40Hz-70Hz
Output Voltage230V
Battery TypeSealed Lead-Acid (SLA)
Communication InterfaceUSB

Related product manuals