Setting the minimum input voltage in bypass mode
Display Setting
You can adjust the minimum input
voltage in bypass mode using ▲ and
▼.
170–220: The voltage can be set from
170 V AC (default) to 220 V AC.
The minimum input voltage in bypass mode must be lower than the minimum
voltage allowed in ECO mode.
Battery capacity setting
Display Setting
You can adjust and set the UPS battery
capacity using ▲ and ▼.
18–999: The capacity can be set from
18 Ah to 999 Ah. (The value is xed at
9 Ah for the UPS with standard backup
time, and the default value is 18 Ah
for the UPS with long backup time.)
Discharge time limit setting
Display
Setting
Set the discharge time limit:
0–999: The time can be set from 0
minutes to 999 minutes.
0: The backup time is not limited
(default).
ECO mode enable/disable
UPS2000-A-(1 kVA-3 kVA)
User Manual 5 Setting Control Panel
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 54