Huawei UPS2000-G-15KRTL - Alarm Handling

Huawei UPS2000-G-15KRTL
194 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mai
n
Men
u
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range Preset Value
Frequency
range
±0.5 Hz, ±1 Hz, ±2 Hz,
±3 Hz, ±4 Hz, ±5 Hz,
and ±6 Hz
±2 Hz
ECO
(congurabl
e after the
inverter
shuts down)
Max. voltage 5%, 6%, 7%, 8%, 9%,
and 10%
10%
Min. voltage 5%, 6%, 7%, 8%, 9%,
and 10%
10%
Frequency
range
±0.5 Hz, ±1 Hz, ±2 Hz,
and ±3 Hz
±2 Hz
Single UPS
ECO
Enabled and Disabled Disabled
Power
segment
Dis. time
thres.
(congurable
in non-
battery
mode)
0–999 minutes 30 min
Dis. volt.
thres.
(congurable
in non-
battery
mode)
1.90–2.25 V/cell 2.00 V/cell
Power
Segment
(congurable
after the
inverter shuts
down)
Enabled and Disabled Disabled
Self-Load Output
power ratio
20%–100% 80%
Self-load
mode
Enabled and Disabled Disabled
Others
(congurabl
e after the
inverter
shuts down)
Recovery
delay time
0–900s 5S
Max. BPS
transfers
1–3 3
Output
transformer
Enabled and Disabled Disabled
UPS2000-G- (6 kVA-20 kVA)
User Manual C LCD Menus and Parameters
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 135