Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0045-04 Charger
alarm
Critical Manual
/Power-
o
The charger in the UPS
stops.
Possible cause:
The charger output is
short-circuited.
The UPS battery
capacity is low.
Measure:
Rectify battery port
short circuits. After
you clear the alarm,
restart the UPS. If
the alarm persists,
contact Huawei
technical support for
repair.
Replace the UPS
battery string.
0045-06 Charger
alarm
Critical Manual
/Power-
o
The charger in the UPS
stops.
Possible cause: The
charger is faulty.
Measure: Contact
Huawei technical
support for repair.
0045-07 Charger
alarm
Critical Manual
/Power-
o
The charger in the UPS
stops. (The 20 kVA has no
action.)
Possible cause: The
charger is faulty.
Measure: Contact
Huawei technical
support for repair.
0045-08 Charger
alarm
Critical Manual
/Power-
o/
Automa
tic
The charger in the UPS
stops.
0045-09 Charger
alarm
Critical Manual
/Power-
o
0045-10 Charger
alarm
Critical
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 160