Mains
input
Bypass
input
AC
load
K
m
1
Q1
K
b
1
8
Wiring
Terminal
AC OUTPUT
AC INPUT
PE
External
Circuit
Breaker
Q1
Mains K
m
1
Bypass K
b
1
15 kVA: 100 A
(D feature);
20 kVA: 125 A
(D feature)
15 kVA:
50 A
(D
feature); 20 kVA:
63 A
(D feature)
15 kVA: 100 A (D feature);
20 kVA: 125 A (D feature)
-
Residual
Current
Circuit
Breaker
-
15 kVA: 300 mA;
20 kVA: 300 mA
15 kVA: 300 mA; 20 kVA:
adjustable from 500 mA
to 1000 mA
-
Cable
Cross
-
Sectional
Area
25 mm
2
10 mm
2
25 mm
2
25 mm
2
Terminal
Type
OT
-25 mm
2
-
M6 terminal
OT
-10 mm
2
-M6
terminal
OT
-25 mm
2
-M6 terminal
OT
-25 mm
2
-M6-90
°
terminal
Three-Phase Input, Single-Phase Output, Two Power Sources