If the inverter has
not started, the
UPS has no output,
and inverter
startup is not
allowed.
If the inverter has
started, inverter
operation is not
affected, but
transfer to bypass
mode is not
allowed.
Possible cause: The bypass input cable
connections do not match the output
system.
Measure: Ensure that the bypass input
cable connections match the output
system.
The power supply
from the UPS and
system is not
affected.
Possible cause: The fan is abnormal.
Measure: Clean off the foreign objects
around the fan. If the alarm persists,
contact
Huawei technical support for
The UPS shuts
down.
The UPS may
transfer to
another working
mode or shut
down.
Possible cause: The inverter output is
short
Measure: Rectify output port short
circuits,
restart the UPS.
If the alarm persists, contact
technical support for repair.
If the bypass is
abnormal, the
UPS may power
off.
The inverter is not started.
• The load exceeds the rated inverter
Check whether other alarms are
generated. If yes, see the other
handling methods.
If no, start the UPS manually.
The UPS may
power off if
batteries are
abnormal.
The mains input is abnormal.
The UPS is in battery self-check
state.
The mains loading capability is
insufficient.
Measures:
• Check the mains input. If the mains
input is abnormal, wait until the
mains input recovers.
Check whether the UPS is in
battery self-check state.
• Reduce the load or replace the UPS
with a larger-capacity UPS.
The power supply
from the UPS and
system is not
affected.
Batteries are not connected.
Batteries are not securely
connected.
Check that batteries are securely
connected.