DBRP
PGM0012A01
STANDARD CASE REV A 8/7/17
Parameter C o e Min Ma Default
A tual ( C) A tual ( F)
Temperature (set point)
roduce (Type I)
--- -50.0°C 50.0°C 2.0°C -2.2 28
Thermostat
Differential r01
0.1 K
20.0K
2.0 K
3.9 7
Max. limitation of setpoint setting
r02 -49.0°C 50°C 50.0°C 4.4 40
Min. limitation of setpoint setting
r03 -50.0°C 49.0°C -50.0°C -3.9 25
Adjustment of temperature indication
r04
-20.0 K 20.0 K 0.0 K 0.0 K
Temperature unit (°C=0/°F=1)
r05 0 1 0 1
Correction of the signal from S4
r09
-10.0 K +10.0 K 0.0 K 0.0 K
Correction of the signal from S3
r10
-10.0 K +10.0 K 0.0 K 0.0 K
Manual service, stop regulation, start regulation (-1, 0,
1)
r12 -1 1 0 1
Displacement of reference during night operation
r13
-10.0 K 10.0 K 0.0 K 0.0 K
Definition and weighting, if applicable, of thermostat
sensors - S4% (100%=S4, 0%=S3)
r15 0% 100% 100% 100%
The heating function is started a number of degrees
below the thermostats cutout temperature
r36
-15.0 K -3.0 K -15.0 K -15.0 K
Activation of reference displacement r 4 0
r39 OFF ON OFF OFF
Value of reference displacement (activate via r39 or DI)
r40
-50.0 K 50.0 K 0.0 K 0.0 K
Alarm
Delay for temperature alarm
A03
0 min 240 min 30 min 30 min
Delay for door alarm
A04
0 min 240 min 60 min 60 min
Delay for temperature alarm after defrost
A12
0 min 240 min 90 min
60
:ig h alarm limit
A13 -50.0°C 50.0°C 8.0°C 7.8 46
;ow alarm limit
A14 -50.0°C 50.0°C -30.0°C -5.6 22
Alarm delay DI1
A27
0 min 240 min 30 min 30 min
Alarm delay DI2
A28
0 min 240 min 30 min 30 min
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36 0% 100% 100% 100%
Compressor
Min. ON-time
c01
0 min 30 min 0 min
1
Min. OFF-time
c02
0 min 30 min 0 min
2
Time delay for cutin of comp.2
c05
0 sec 999 sec 0 sec 0sec
Compressor relay 1 must cutin and out inversely
(NC-function)
c30 0
OFF
1
ON
0
OFF
0
OFF
Defrost
Defrost method (none/<;/=AS/>RIN<)
d01 no bri < ; <;
Defrost stop temperature
d0 2 0 .0°C 25.0°C 6.0°C 12.2 54
Interval between defrost starts
d03
0 hours 240 hours 8 hours
6
Max. defrost duration
d04
0 min 180 min 45 min
30
Displacement of time on cutin of defrost at start-up
d05
0 min 240 min 0 min 0min
Drip off time
d06
0 min 60 min 0 min 0min
Delay for fan start after defrost
d07
0 min 60 min 0 min 0min
Fan start temperature
d0 8 -15.0°C 0.0°C -5.0°C -5.0°C
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
d09 0 2 1 1
Defrost Sensor (0=time, 1=S5. 2=S4)
d10 0 2 0 0
ump down delay
d16
0 min 60 min 0 min 0min
Drain delay
d17
0 min 60 min 0 min 0min
Max. aggregate refrigeration time between two
defrosts
d18
0 hours 48 hours 0 hours
Defrost on demand - S5 temperature's permitted
variation during frost build-up. On central plant choose
20 K (=off )
d19
0.0 K 20.0 k 20.0 K
Delay of hot gas defrost
d23
0 min 60 min 0 min 0min
Fan
Fan stop at cutout compressor
F01 no yes no no
Delay of fan stop
F02
0 min 30 min 0 min 0min
Fan stop temperature (S5)
F0 4 -50.0°C 50.0°C 50.0°C 50.0°C
Controller Parameters
24