Control connections
Manual high speed
(A1-A2)
Cooling recycling. Will give adjusted max speed if run (5-6)
is closed.
Defrosting. Will give adjusted min. speed if run (5-6) is
closed.
Adjusted to central control.
(0-5V, 0-10V, 1-5V, 2-10V, 5-10V, 10-0V, 10-2V, 10-5V,
0-20 V Phase cut, 0-20mA, 4-20mA).
See adjusting DIP-switches, page 4.
Frequency
measurement
(3-4)
0-10VDC relates to 0-100Hz. Dvs 0,5V = 5Hz, 5V = 50Hz.
The speed of the rotor is proportional to the frequency.
Must be closed if external start is not being used.
Must be closed if the thermal contact in the motor is not
being used.
White wire to number 9, brown wire to number 10.
The magnet should be mounted with southpole against the
transmitter. Max distance 15 mm.
The inverter trips if it does not receive pulses every 5
minutes. The function can be disabled. See DIP-switches,
page 4.
Remote reset of alarm. The inverter resets automatically
when input power is disconnected.
Connected between 14-15 when alarm or power is off.
Connected between 16-17 when run is enabled.
Max. 8A/250V AC.
Manual test
The motor rotates with adjusted maximum speed.
The motor rotates with adjusted minimum speed.