Adjustments
Boost
Adjusts the low speed torque. Adjusted before delivery. May be
increased if needed but will increase the motor temperature at low
speed.
Acc
Time of acceleration (0-30 sec).
Adjusted to max. before delivery. Will not require adjustment.
Ret
Retardation time (0-30 sec).
Adjusted to max. before delivery. Will not require adjustment.
Threshold value
The inverter does not start until the speed reference signal exceeds
the threshold value, which is adjustable between 0 and 20 % of the
maximum input signal. For example at chosen input signal 0-10 V
the threshold value is adjustable between 0-2 V.
Min rpm
Min. speed (1-20Hz). Adjusted before delivery to 4 Hz.
Max rpm
Max. speed (40-100Hz). Adjusted before delivery to 50 Hz.
Adjusting DIP-switches
1
2
3
4
5
6
7
8
Potentiometer
0
0
0
0
0
0
0-5 V
0
0
0
0
0
0
0-10 V
1
0
0
0
0
0
0-20 V
0
1
0
0
0
0
1-5 V
0
0
1
0
0
0
2-10 V
1
0
1
0
0
0
5-10 V
1
0
0
1
0
0
10-0 V
1
0
0
0
0
1
10-2 V
1
0
1
0
0
1
10-5 V
1
0
0
1
0
1
0-20 mA
0
0
0
0
1
0
4-20 mA
0
0
1
0
1
0
Cleaning function off
0
Cleaning function on
1
Rotation monitor off
0
Rotation monitor on
1
DIP-switch
ON (1)
1...............8
OFF (0)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC control Variotron VVX MiniMax VK and is the answer not in the manual?

IBC control Variotron VVX MiniMax VK Specifications

General IconGeneral
BrandIBC control
ModelVariotron VVX MiniMax VK
CategoryControl Unit
LanguageEnglish

Related product manuals