TROUBLESHOOTING
DC SERIES COMBI BOILERS DC 23-84, DC 29-106, DC 33-124, DC 33-160
5.4.8 Hot Water Does Not Reach Temperature
POSSIBLE CAUSES SOLUTION
DHW ow to high. Adjust the inlet assembly, insert a ow restriction.
Temperature setting for water circuit too low. Adjust the hot water circuit, depending on the desired temperature and
system conguration. See 2.3.4 Table of Programmable Parameters
Water temperatures are set incorrectly Target water temperature is set higher than the maximum water
temperature.
No heat transfer as a result of lime scale or
fouling in the heat exchanger DHW side.
Descale or ush the exchanger DHW side.
Cold water temperature <5°C.