IBM 1000VA and 1500VA LCD Tower UPS 7
Table 4. Specifications (continued)
Specification IBM 1000VA
LCD Tower
UPS (100 V)
IBM 1000VA
LCD Tower
UPS (120 V)
IBM 1000VA
LCD Tower
UPS (230 V)
IBM 1500VA
LCD Tower
UPS (100 V)
IBM 1500VA
LCD Tower
UPS (120 V)
IBM 1500VA
LCD Tower
UPS (230 V)
Communications and management
USB HID port Yes Yes Yes Yes Yes Yes
RS-232 serial
port
Yes Yes Yes Yes Yes Yes
Ethernet port Optional using Network Management Card, 46M4110
Environmental
Monitoring
Probe
Optional Environmental Monitoring Probe, 46M4113
Management
software
included
IBM UPS Manager
Control panel Intelligent three-button, dual color, and backlit graphical LCD displays vital UPS status in nine
languages
Audible alarm Alarm when on battery: Distinctive low-battery alarm
Remote Power
Off
Remote Emergency Power Off (REPO) port
Surge Protection and Filtering
Surge energy
rating
1200 Joules 2400 Joules 1200 Joules 2400 Joules
Filtering ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Table 5 lists the expected period that the IBM 1000VA LCD Tower UPS models will operate solely on
batteries.
Table 5. IBM 1000VA LCD Tower UPS runtime chart
Load (%) Load (VA) Load (Watts) Run time (minutes)
25 250 VA 188 W 25
50 500 VA 375 W 15
75% 750 VA 573 W 7
100% 1000 VA 750 W 6