To connect the dc power distribution panel (feature code 6117), see “Connecting a -48V DC Power
Distribution Panel (PDP), feature code 6117” on page 44.
Connecting the -48V DC Power Distribution Panel (PDP), feature code EPB8
Some rack models (such as the 7014-T00) can support a DC power conguration for systems that require
DC power. This procedure describes how to connect your power to the power distribution panel.
Note: You are responsible for providing and connecting the -48V DC power source and -48V DC power
return cables from your source -48V DC to the bus bars in the power distribution panel. You are also
responsible for connecting the ground cable to the rack frame.
Sections of the following instructions are from the copyrighted Telect Dual-Feed 600A Load Center Frame
(600CB10 and 600CB12) User manual and are reproduced in part with the written permission of Telect,
Inc. Additional details on the Telect Dual-Feed 600A Load Center Frame can be found in the Telect User
manual. For more information, see Dual-Feed 600A Load Center Frame.
Connecting DC power to the PDP
Learn more about how to connect your DC power to the PDP.
Procedure
1. Remove the cable channel cover. To remove the cable channel cover, perform the following steps:
a. Loosen the four retaining screws (5).
b. Align the larger openings in the cover (6) with the retaining screw heads.
c. Lift the cover up to clear the retaining screws and remove it.
26
Power Systems: Racks and rack features