005 (continued)
The dc indicator on a power supply is OFF. Replace the power supply. (See
Chapter 4, “Multiaccess Enclosure FRU Exchange” on page 4-1.)
Is the problem corrected?
Yes No
006
Contact your support center for assistance.
007
Restart the verification procedure. Go to Step 001 on page 3-6.
008
The Overcurrent LED on a power supply is ON.
Are all adapter yellow fault LEDs OFF?
Yes No
009
Remove the adapter with a yellow fault LED ON, then press Reset on the
power supply.
Is the Overcurrent LED now OFF?
Yes No
010
Replace the power supply. See Chapter 4, “Multiaccess Enclosure
FRU Exchange” on page 4-1. Restart the verification procedure. Go
to Step 001 on page 3-6.
011
Replace the adapter. See Chapter 4, “Multiaccess Enclosure FRU
Exchange” on page 4-1. Restart the verification procedure. Go to Step 001
on page 3-6.
012
The problem may be with the fan tray. Remove it (see “Exchanging the Fan Tray”
on page 4-40) and press Reset on the power supply.
Does this correct the problem?
Yes No
013
Re-install the fan tray. Contact your support center.
014
Replace the fan tray. See Chapter 4, “Multiaccess Enclosure FRU Exchange”
on page 4-1.
Restart the verification procedure. Go to Step 001 on page 3-6.
Chapter 3. Multiaccess Enclosure Problem Determination 3-9