Table 69. Weight distribution distances for racks when loaded
Rack System
weight
1
Width
2
Depth
2
Weight distribution distance
3
Front and back Left and right
7014-T00
4
816 kg (1795
lb)
623 mm (24.5
in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
467.4 mm (18.4 in)
7014-T00
5
816 kg (1795
lb)
623 mm (24.5
in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
0
7014-T00
6
816 kg (1795
lb)
623 mm (24.5
in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
559 mm (22 in)
7014-T42 and
0553
4
930 kg (2045
lb)
623 mm (24.5
in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
467.4 mm (18.4 in)
7014-T42 and
0553
5
930 kg (2045
lb)
623 mm (24.5
in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
0
7014-T42 and
0553
6
930 kg (2045
lb)
623 mm (24.5
in)
1021 mm
(40.2 in)
515.6 mm (20.3 in), 477.5
mm (18.8 in)
686 mm (27 in)
Notes:
1. Maximum weight of fully populated rack, units are lb with kg in parentheses.
2. Dimensions without covers, units are mm with inches in parentheses.
3. The weight distribution distance in all four directions is the area around the rack perimeter (minus covers)
necessary to distribute the weight beyond the perimeter of the rack. Weight distribution areas cannot overlap
with adjacent computer equipment weight distribution areas. Units are inches with mm in parentheses.
4. Weight distribution distance is 1/2 the service clearance values shown in the figure plus cover thickness.
5. No left and right weight distribution distance.
6. Left and right weight distribution distance required for a 70 lb/ft
2
raised floor loading objective.
The following table shows the necessary floor loading for the 7014-T00, 7014-T42 and 0553 racks when
loaded.
Table 70. Floor loading for racks when loaded
Rack Floor loading
Raised kg/m
1
Non-raised kg/m
1
Raised lb/ft
1
Non-raised lb/ft
1
7014-T00
2
366.7 322.7 75 66
7014-T00
3
734.5 690.6 150.4 141.4
7014-T00
4
341 297 70 61
7014-T42 and 0553
2
403 359 82.5 73.5
7014-T42 and 0553
3
825 781 169 160
7014-T42 and 0553
4
341.4 297.5 70 61
Notes:
1. Dimensions without covers, units are mm with inches in parentheses.
2. Weight distribution distance is 1/2 the service clearance values shown in the figure plus cover thickness.
3. No left and right weight distribution distance.
4. Left and right weight distribution distance required for a 70 lb/ft
2
raised floor loading objective.
Related reference:
“Model 7014-T42, 7014-B42, and 0553 rack” on page 40
Hardware specifications provide detailed information for your rack, including dimensions, electrical,
power, temperature, environment, and service clearances.
Site and hardware planning 47

Table of Contents

Other manuals for IBM 9008-22L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 9008-22L and is the answer not in the manual?

IBM 9008-22L Specifications

General IconGeneral
BrandIBM
Model9008-22L
CategoryServer
LanguageEnglish

Related product manuals