EasyManuals Logo
Home>IBM>Power Supply>9009-22A

IBM 9009-22A Site And Hardware Planning

IBM 9009-22A
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
Table 8. Environment requirements (continued)
Environment requirements
Properties Recommended Allowable
2,3,4
ASHRAE class A2 (Fourth edition)
Airflow direction Front-to-back
Temperature 18.0°C – 27.0°C (64.4°F –
80.6°F)
10.0°C – 35.0°C (50.0°F –
95.0°F)
Low end moisture -9.0°C (15.8°F) dew point -12.0°C (10.4°F) dew point and
8% relative humidity
High end moisture 60% relative humidity and 15°C
(59°F) dew point
85% relative humidity and
21.0°C (69.8°F) dew point
Maximum altitude 3050 m (10,000 ft)
Allowable environment (nonoperating)
5
Temperature 5°C - 45°C (41°F - 113°F)
Relative humidity 8% to 85%
Maximum dew point 27°C (80.6°F)
Environment (shipping)
Temperature -40.0°C to 60.0°C (-40°F to 140°F)
Relative humidity 5% - 100% (no condensation)
Maximum wet bulb temperature 29.0°C (84.2°F)
Environment (storage)
Temperature 1°C - 60°C (33.8°F - 140°F)
Relative humidity 5% - 80% (no condensation)
Maximum wet bulb temperature 29°C (84.2°F)
Site and hardware planning 9

Other manuals for IBM 9009-22A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 9009-22A and is the answer not in the manual?

IBM 9009-22A Specifications

General IconGeneral
BrandIBM
Model9009-22A
CategoryPower Supply
LanguageEnglish

Related product manuals