IBM System x3500 M3 29
Physical and electrical specifications
Tower:
Width: 218.0 mm (8.6 in)
Depth: 767.0 mm (30.2 in)
Height: 440.0 mm (17.3 in)
Weight:
27.40 kg (60.4 lb) (minimum configuration)
38.90 kg (85.6 lb) (maximum configuration)
Rack (using the Tower-to-Rack Conversion Kit, 69Y0893):
Width: 424.0 mm (16.7 in)
Depth: 702.0 mm (27.6 in)
Height: 218.0 mm (8.6 in)
Weight:
26.20 kg (57.7 lb) (minimum configuration)
37.20 kg (82.0 lb) (maximum configuration)
Supported environment:
Air temperature
Server on: 10 - 35° C (50 - 95° F); altitude: 0 - 915 m (3,000 ft)
Server on: 10 - 32° C (50 - 90° F); altitude: 915 m (3,000 ft) - 2,134 m (7,000 ft)
Server off: 5 - 45° C (41 - 113° F)
Shipment: -40 - 60° C (-40 - 140° F)
Humidity
Server on: 20 - 80%; maximum dew point 21° C; maximum rate of change 5° C/hr
Server off: 8 - 80%; maximum dew point 27° C
Electrical
100 - 240 V ac; 50 - 60 Hz; 11 - 5.5 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.60 kVA
Maximum configuration: 1.10 kVA
Btu output
Ship configuration: 2013 Btu/hr (590 watts)
Full configuration: 3610 Btu/hr (1056 watts)
Acoustical noise emission levels
5.5 bels (idling)
6.0 bels (operating)