EasyManuals Logo

ICP HMC018KD User Manual

ICP HMC018KD
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
- 56 -
8. The phenomena in case of connecting error
INDOOR UNIT
Connector Type
Condition
Open and connecting error
Open
Open
Open
Open
Short between terminals
(¤Øand ¤Œ) of ROOM-TH.
Short between terminals
(¤ and ¤Ł) of PIPE-TH.
Short between terminals
• The same as the phenomenon of Outdoor Unit.
• The up/down vane does not operate.
• The up/down vane does not smoothly operate.
• It does not operate with a remote controller.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds).
• The compressor operates continuously regardless
of the setting temperature and the variation of room
temperature.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds)
• Continuous operation
• The operation indicator blinks once.
• The compressor and the outdoor fan stop.
• The indoor fan speed is low.
• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.
CN-DC/DC
CN-MOTOR
CN-UP/DOWN
CN-DISP
CN-TH
¤ Blue
¤Ł Black
¤Ø Brown
¤Œ Red
Phenomena
¤ ¤Ł¤Ø¤Œ¤º
On for 0.5 second
Off for 3 seconds

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICP HMC018KD and is the answer not in the manual?

ICP HMC018KD Specifications

General IconGeneral
BrandICP
ModelHMC018KD
CategoryHeat Pump
LanguageEnglish

Related product manuals