Two designs duct version
(
I
LK)
wall mounting
(ILW)
Different
physical
outputs
humidity and temperature and all
hx values
1)
Output signals RS232 with ASCII protocol
RS485 with Modbus RTU protocol
Special versions sealing for increased
requirements, e.g. condensation
sealing against vibrations
Filter protective basket ZE07 (IP 00)
lter with membrane ZE08 (IP30)
PTFE sintered lter ZE05 (IP65)
Product info sheet IL Series digital
Humidity/-temperature sensors for digital data
transfer RS485 / MODBUS-RTU or RS232 for
use in heating, ventilation and air conditioning
Measuring medium air, pressureless,
non-aggressive, non-condensing
Min. air speed 0.5 m/s
Operating temperature -40...+80°C
Storage temperature -40...+85°C
Degree of protection of measuring head
with protective basket ZE07 IP00
with membrane lter ZE08 IP30
with PTFE sintered lter ZE05 IP65
Degree of protection housing IP65
Material of housing PC (light grey / white)
General data
Power supply, external 6...30 VDC
Max. transfer distance RS232/RS485 15m/1000 m
Consumption of electronics < 1,0 mA
Directive about electromagnetic compatibility 2014/30/EU
DIN EN 61326-1 ............................................. issue 07/13
DIN EN 61326-2-3 .......................................... issue 07/13
Humidity
Sensing element calibrated sensor chip calHT
Output range 0...100 %rh
Accuracy
30...80 %rh at 10...40°C ±3 %rh
< 30 %rh or > 80 %rh at 10...40°C ±5 %rh
Inuence of temperature < 10°C or > 40°C typ. ±0.06 %rh/K
Technical data
Temperatur
Sensing element calibrated sensor chip calHT
Output ranges -40...+85°C
Accuracy
at 10...40°C ±0.8 K
<10°C and >40°C see diagramm
Electrical data
1) The accuracy of the calculated values depends on both the opera-
ting point in accordance with the hx diagram and on the primary values
measured. The hx processor operates in the range -30°C < T < +70°C,
5% rh<F<95% rh. Values outside this range are not calculated, the last
valid value is displayed. Normal atmospheric pressure of 1013.25 mbar
is used when calculating the hx values.
ILK
ILW