EasyManuals Logo

ICS IL Series User Manual

Default Icon
9 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Raasdorfer Str. 18
07987 Mohlsdorf-Teichwolframsdorf
Tel.: 03661/627040 · Fax: 6270420
MELA Sensortechnik GmbH
Marion Scholz
1800 (L)
BKKM.02.AK-01.8
Table 2 lists all the possible alarm register values when measuring temperature (reg. no. 2).
Alarm code Meaning
0 no alarm, the temperature value is within the limits
3 no sensor element detected
Table 2 - alarm codes temperature
Table 3 lists all the possible alarm register values when measuring humidity (reg. no. 5).
Alarm code Meaning
0 no alarm, the humidity value is within the limits
3 Wire break or no sensor element detected
Table 3 - alarm codes humidity
Table 4 lists all the possible alarm register values of the hx processor (reg. no. 20).
Alarm code Meaning
0 no alarm, input values are within the limits
1 max. input value of humidity 95%rh and/or temperature +70°C is exceeded
2 min. input value of humidity 5%rh and/or temperature -30°C is below limit
3 hx processor deactivated
Table 4 - alarm codes hx processor
The Modbus address can be modied at any time via write access to the address register (reg. no. 205). Permissi-
ble slave addresses are within the 1...247 range. Using address 0 as a slave address is not permissible. Addresses
within the 248…255 range are reserved for special Modbus services and their use as a slave address is not permis-
sible either. Address 1 is pre-dened.
Conguration of Modbus parameters
In standard mode (and in the network if required), the Modbus address for all sensors can be modied by entering
an appropriate write command. The write command will still be acknowledged using the old address. The sensor can
then be accessed immediately via the new address.
Further conguration of Modbus parameters, such as address, baud rate, parity and stop bits is only possible with the
suitable setup cable BKKM.02.AK-01.8 (see accessories on page 2). These settings are then made from a PC via the
ModSens-Setup software available for download. For this, the sensors must not be in the network.
.
Fig. 1
The ModSens Setup software and the documentation are available on our Homepage as a free download
(http://melasensor.de/download/).
Service
USB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICS IL Series and is the answer not in the manual?

ICS IL Series Specifications

General IconGeneral
BrandICS
ModelIL Series
CategoryTemperature Controller
LanguageEnglish